變壓器強油循環風冷卻器工作與備用電源自動切換回路
如下圖所示,變壓器投入電網之前,先將SA開關手柄置于I工作II備用,或者II工作I備用位置。
當變壓器投入電網時,1KM常閉觸點接通;1KV1、2KV1帶電,常開觸點接通,起動1KV、2KV使常閉觸點斷開;假定SA開關手柄在I位,則SA1-2接通起動1KL接觸器,1KL主觸頭閉合由工作電源(I)供電。2KL線圈回路被1KL常閉觸點斷開(閉鎖了)。
當工作電源(I)由于某種原因停電,1KL線圈斷電,1KL主觸頭斷開工作電源(I),1KL常閉觸點接通,1KV斷電常閉觸點接通,再經SA5-6觸點動作2KL接觸器,2KL主觸頭閉合由工作電源(II)供電。
假如工作電(dian)(dian)(dian)源(yuan)(yuan)(I)恢復(fu)供(gong)電(dian)(dian)(dian)時,1KV1動(dong)作起動(dong),1KV動(dong)作,1KV常閉觸點(dian)斷(duan)開使2KL斷(duan)電(dian)(dian)(dian),2KL的主(zhu)觸頭斷(duan)開工作電(dian)(dian)(dian)源(yuan)(yuan)(II),2KL常閉觸點(dian)起動(dong)1KL,1KL的主(zhu)觸頭閉合(he)由工作電(dian)(dian)(dian)源(yuan)(yuan)(I)供(gong)電(dian)(dian)(dian)。